Electrical takeoff
A reference on how electrical work is measured: how conduit and wire lengths are built up along the centre line, why wire is longer than conduit, how devices and fixtures are counted, and the boundaries, deductions, and published standards that govern each quantity, with regional differences.
Electrical takeoff is two measuring jobs at once. One is linear: the conduit, raceway, and wire that carry power around a building, measured in length. The other is by count: the receptacles, switches, light fixtures, and panels, counted each by type. Both are easy to under-measure for the same reason, which is that a floor plan shows only the flat, horizontal picture of an installation that climbs, drops, and turns in three dimensions.
This guide sets out how those quantities are built up and the conventions behind them. The linear work follows the same centre-line rule that standards bodies apply to all building services: measure along the developed length of the run as it is actually installed. In the UK this is RICS NRM2 Work Section 39; Australia and New Zealand use the AIQS and NZIQS ANZSMM; the United States has no statutory method and works to convention anchored in the National Electrical Code (NEC, NFPA 70). Counts are enumerated by device and schedule type, with distribution equipment enumerated separately from devices, fixtures, and raceway.
The conduit run is a box-to-box centre line
A conduit run is measured along the centre line of the run, from the geometric centre of one enclosure to the centre of the next, not the box faces. Stopping at a face drops the pipe inside each enclosure, a loss that repeats on every run. RICS NRM2 Work Section 39 measures services net along the centre line, and ANZSMM enumerates points between boards along the route. Conduit is routed at right angles, parallel to walls and structure, never on a diagonal, so measuring the straight-line hypotenuse is the most common cause of under-measurement: sum the orthogonal legs along the actual route.
Nothing is deducted from a raceway run. The centre line passes straight through every fitting and into each enclosure, and boxes and fittings are counted as separate items rather than subtracted. The only adjustments are additions: a small allowance per bend for the take-up of the radius, and the vertical legs below.
Add the vertical legs the plan does not show
A floor-plan trace captures only the horizontal part of the run. The raceway also drops to each device, climbs risers up walls and columns, and stubs up through slabs. These vertical legs are invisible on plan and are the most-missed conduit quantity, so they must be added; standard methods measure the developed, fully installed length. Feeders, risers, and the service entrance must be read off the one-line and riser diagrams, since the vertical pipe between distribution levels does not appear on a plan view.
Drop heights come from the project mounting-height schedule when one is given. Otherwise, trade practice centres a receptacle box at about 18 inches above finished floor and a switch box at about 48 inches; the NEC sets no fixed general-use mounting height. Accessibility rules set the band, not the default: ICC A117.1 and the ADA Standards require accessible operable parts within a reach range of 15 to 48 inches above finished floor. In the UK, Approved Document M places the centre line of switches and socket outlets between 450 and 1200 millimetres above finished floor in new dwellings, and national accessibility codes elsewhere set their own bands.
The 360-degree bend limit and pull boxes
The NEC limits the total bends between pull points to 360 degrees, the equivalent of four quarter-bends, set in the .26 section for each raceway type: 358.26 for EMT, 344.26 for rigid metal conduit, 342.26 for intermediate metal conduit, 348.26 for flexible metal conduit, 352.26 for PVC, and 362.26 for electrical nonmetallic tubing. When the route plus offsets would exceed 360 degrees, a pull box must be inserted. A pull box splits the run into two separately measured segments and adds one enclosure to the count; pull boxes are counted each and never measured into the conduit length. The UK (BS 7671) and Australia and New Zealand (AS/NZS 3000) reach the same intent through required draw-in and inspection boxes rather than a fixed degree figure.
Wire is a separate, longer quantity than conduit
Never reuse conduit length as wire length. Conductors continue past the end of the conduit into each enclosure for terminations and splices, so wire footage always exceeds conduit footage. The NEC requires at least 6 inches (150 millimetres) of free conductor at every outlet, junction, and switch point, and large boards and switchgear need extra slack for make-up; in the UK, BS 7671 calls for adequate conductor length at accessories, with a tail of roughly 150 millimetres typical and larger loops at boards. Wire is then multiplied by the number of conductors in each raceway, since one conduit carries several, and carries its own allowance for reel-end cut-offs, pulling spoilage, and termination loops. Only the per-box minimum is fixed by code; the larger make-up loops at panels and switchgear are practical allowances.
Two takeoff methods, chosen by purpose
There are two accepted ways to measure circuits. The detailed method traces every box-to-box segment and sums them: most accurate, slowest, and the right choice for procurement and ordering. The homerun-plus-average method measures the homerun from the panel to the farthest device, then adds an average footage per device for the daisy-chained branch; it is faster and common in early US bidding. That average footage is not fixed by any standard, varying widely with occupancy (residential, commercial, or industrial), ceiling height, and device density, so it should be treated as a tunable figure calibrated against project history. In the United States, labour is applied through the NECA Manual of Labor Units, which prices installed raceway per 100 feet with normal, difficult, and very difficult tiers.
Counting devices by yoke and by type
Device counts feed both fixture procurement and the branch-circuit derivation, so they are counted by device and segregated by schedule type. Receptacles are counted by device: a duplex is one, and special-purpose receptacles (range, dryer, 208 to 240 volt), GFCI, weatherproof, and floor boxes are each separate count lines by type. Switches, luminaires, data and AV jacks, and blank junction boxes are excluded. In the UK and in Australia and New Zealand, socket outlets are often enumerated by gang, so a twin socket is one accessory but two outlets.
Switches are counted per yoke or strap, not per box, so a three-gang bank counts as three. A multi-way control has a device at each end and both are counted: the US three-way and four-way are the UK two-way and intermediate. Dimmers, occupancy sensors, and timers are separate count lines. Luminaires are counted each by their fixture-schedule type tag; a 2 by 4 troffer is one fixture even though it may displace several ceiling tiles. Continuous strip, cove, and row fixtures can instead be measured in length by type, and exit signs, emergency lights, and exterior fixtures are separate lines. Standards distinguish the lighting point (the wiring outlet) from the luminaire (the fitting), and NRM2 and ANZSMM enumerate both.
Distribution boards, grounding, and other raceways
Distribution equipment is a distinct enumerated item, separate from devices, fixtures, and raceway. Each panelboard, switchboard, switchgear lineup, or distribution board is counted, described by type, number of ways or poles, and rating. RICS NRM2 enumerates boards by number with their way count and rating, and ANZSMM lists them on the distribution schedule. Read this off the one-line and riser diagrams, never the floor plan, because each board is a high-cost line that is easy to omit.
Grounding and bonding is its own system under NEC Article 250: the grounding-electrode conductor, the electrodes (rods, plates, or a concrete-encased electrode), bonding jumpers, and the equipment-grounding conductor pulled with each raceway all add quantity that counting phase and neutral conductors will miss. The equipment-grounding conductor adds wire footage unless the metallic raceway itself serves as the ground, and the electrode hardware is a separate enumerated item; in the UK, BS 7671 measures circuit protective conductors and main bonding separately by size and type.
Cable tray, busway and bus duct, wireway, and surface raceway are measured differently from conduit and must not be folded into conduit length. They are measured in length by system, size, or rating, stating jointing, spacing, and supports, with their fittings (elbows, tees, tap-off boxes, end feeds, and supports) enumerated separately. RICS NRM2 measures tray and trunking in metres stating jointing, spacing, and supports, and busbar trunking by length and rating; the relevant NEC articles are 392 for cable tray, 368 for busway, and 376 and 378 for wireways.
Underground, demolition, and branch versus feeder
Underground electrical is measured in length by configuration, stating the number and size of ducts, while the trench excavation, bedding, backfill, and concrete encasement are measured separately by burial-depth band. NEC Table 300.5 sets the minimum cover by wiring method and circuit type, which fixes the depth band. Because the trench often belongs to the site-utilities scope, take it off in exactly one place to avoid double-counting, and add a concrete-volume line where the duct bank is encased.
Retrofit and renovation work classifies each item into one of three states: existing-to-remain (no takeoff), remove (a demolition line measured for removal labour and disposal), and reuse (existing raceway or boxes re-pulled). Reusing an existing raceway reduces new conduit length but still needs new wire pulled through it. RICS NRM2 measures removal and alteration as separate items from new installation. Drive this from the existing-conditions survey, not the plan alone.
Branch wiring and feeders are taken off separately. Branch circuits use small conduit and wire to devices; feeders, risers, and the service entrance use large conduit and wire between gear, with very different sizes, labour rates, and routing, so merging them corrupts the estimate. Branches come off the floor plan; feeders, risers, and service come off the one-line and riser diagrams. Segregate conduit by raceway type (EMT, rigid, intermediate, PVC, or flex) and trade size as well, since each carries its own material and labour rate.
Units, ordering allowances, and regional differences
Raceway is a linear quantity: imperial regions measure conduit in linear feet, with NECA labour priced per 100 feet, and metric regions in linear metres along the centre line, in each case segregated by raceway type and trade size and rounded to the region's convention. Ordering allowances apply to material quantities only, never to the measured boundary or to billed-in-place quantities. Conduit carries a waste allowance for cut-offs, bend spoilage, and damaged sticks, often around 10 percent and higher on bend-heavy runs, and wire carries a slightly higher waste-and-make-up allowance because of pulling loss and termination loops. These percentages are practical ordering allowances, not standard figures, so calibrate them against project history.
Regional methods differ in emphasis. The United States has no statutory method, works to NEC-anchored convention in imperial units, and tolerates the homerun-plus-average shortcut. The UK is the most codified: RICS NRM2 Work Section 39 measures services net along the centre line in metres, enumerates accessories and luminaires by number, and separates final circuits from sub-mains, with BS 7671 governing draw-in boxes and conductor tails. Australia and New Zealand follow ANZSMM with a distribution-schedule approach that enumerates every point by location and type, metric throughout. Canada is hybrid: metric drawings, imperial trade sizes, NEC-aligned practice, and British-origin quantity-surveying methods. European countries use national methods such as the DIN-based German standards, metric, with device heights set by national accessibility norms. International work harmonises on ICMS, measuring services in centre-line metres. Exayard reads the plan set, the one-line, and the schedules, applies these rules by raceway type and device type, and records the standard behind each quantity so it can be checked and defended.
How it varies by region
Standards of measurement differ by market. These defaults switch when you set your region in Exayard.
| What varies | Region | Default | Basis |
|---|---|---|---|
| Where a conduit/raceway run starts and stops | United Kingdom | Center of enclosure to center of enclosure | RICS NRM2 Work Section 39, services measured net along the centre line including runs through fittings |
| Where a conduit/raceway run starts and stops | Australia / NZ | Center of enclosure to center of enclosure | AIQS/NZIQS ANZSMM, final-circuit cable/conduit described and measured between distribution board and points |
| Default device rough-in heights (for vertical-leg derivation) | United Kingdom | 450-1200 mm | Approved Document M (Access to and use of buildings), switches/socket-outlets located with their centre line between 450 mm and 1200 mm above finished floor level in new dwellings |
| Default device rough-in heights (for vertical-leg derivation) | Europe | 850-1050 mm | National accessibility norms (e.g. DIN 18040-1/-2 in Germany), operable controls reportedly in the ~850, 1050 mm band |
| Pull box insertion at the 360-degree bend limit | United Kingdom | 360 degrees | BS 7671 (IET Wiring Regulations) / manufacturer conduit guidance, equivalent draw-in box practice |
| Pull box insertion at the 360-degree bend limit | Australia / NZ | 360 degrees | AS/NZS 3000 Wiring Rules, draw-in points to permit cable installation |
| Conduit/raceway unit of measure and rounding | United States | Linear feet (LF), priced per 100 ft | US customary; NECA MLU per 100 ft |
| Conduit/raceway unit of measure and rounding | Canada | Linear feet (LF), priced per 100 ft | Mixed, metric drawings, imperial materials; conduit commonly ordered in feet |
| Conduit/raceway unit of measure and rounding | United Kingdom | Linear metres (m) | RICS NRM2, metres |
| Conduit/raceway unit of measure and rounding | Australia / NZ | Linear metres (m) | ANZSMM, metres |
| Conduit/raceway unit of measure and rounding | Europe | Linear metres (m) | National SMMs, metres |
| Conduit/raceway unit of measure and rounding | International | Linear metres (m) | ICMS 3, metres |
| What counts as a receptacle/outlet | United Kingdom | One count per gang/strap | ANZSMM/NRM2 enumerate socket-outlets by number and gang (single/double/twin) |
| What counts as a receptacle/outlet | Australia / NZ | One count per gang/strap | ANZSMM, socket outlets enumerated; GPOs by number of outlets |
| What counts as a switch (and how multi-way is handled) | United Kingdom | One count per switch yoke/strap | NRM2, one-way, two-way and intermediate switches enumerated by number |
| What counts as a switch (and how multi-way is handled) | Australia / NZ | One count per switch yoke/strap | ANZSMM, switch outlets enumerated; gang count described |
| What counts as a light fixture (luminaire) | United Kingdom | One count per luminaire, grouped by fixture type tag | NRM2, luminaires/lighting points enumerated (nr) by type |
| What counts as a light fixture (luminaire) | Australia / NZ | One count per luminaire, grouped by fixture type tag | ANZSMM, light fittings enumerated from distribution sheet by type |
Key terms
- Where a conduit/raceway run starts and stops
- A raceway run is a centerline path between enclosures; choosing the enclosure CENTER (not its face) keeps the convention consistent with how the field measures box-to-box and avoids losing the short stub inside the box.
- Conduit routing geometry (right-angle vs straight-line)
- Conduit is installed parallel to building lines (along walls/structure, turning at 90°), not diagonally point-to-point.
- Add vertical legs (risers, drops, stub-ups) to the plan run
- A floor-plan trace captures only the horizontal leg.
- Default device rough-in heights (for vertical-leg derivation)
- Vertical-leg length depends on device height.
- Homerun + branch take-off method
- Two legitimate methods coexist.
- Average raceway/wire footage per device (branch allowance)
- Repetitive branch wiring is often estimated as a flat footage allowance per outlet/switch/fixture rather than traced.
- Bend / direction-change length allowance
- Each 90° change of direction consumes more conduit than the orthogonal corner-to-corner sum implies (the bend has a radius).
- Pull box insertion at the 360-degree bend limit
- NEC caps total bends between pull points at the equivalent of four quarter-bends (360°).
- Deductions for boxes, fittings, and openings
- The centre-line measurement runs straight THROUGH every fitting and into the enclosure; boxes and fittings are counted as separate items, never subtracted from the LF.
- Conduit material waste/scrap factor
- Cut-offs, bend spoilage, and damaged sticks mean ordered conduit exceeds measured length.
- Wire/conductor length is separate from and longer than conduit
- Conductors continue PAST the conduit end into each enclosure for terminations/splices, so wire footage always exceeds conduit footage.
- Wire/conductor waste and make-up factor
- Beyond per-box slack, conductors incur reel-end cut-offs, pulling spoilage, and make-up at terminations.
Standards referenced
- RICS NRM2, Work Section 39 (Electrical services)
- AIQS/NZIQS ANZSMM (Australian and New Zealand Standard Method of Measurement), Electrical services, final circuits
- NEC (NFPA 70)
- ICC A117.1 / ADA Standards
- ADA Standards for Accessible Design (28 CFR Part 36), U.S. Access Board
- ICC A117.1 (Accessible and Usable Buildings and Facilities)
- UK Approved Document M (Access to and use of buildings)
- NECA Manual of Labor Units (MLU)
- AIQS/NZIQS ANZSMM
Frequently asked questions
Where should a conduit run begin and end, box center, box face, or device symbol?
A raceway run is a centerline path between enclosures; choosing the enclosure CENTER (not its face) keeps the convention consistent with how the field measures box-to-box and avoids losing the short stub inside the box. Stopping at the box face systematically under-measures each run.
Should conduit length follow right-angle routes along structure, or the straight-line distance between boxes?
Conduit is installed parallel to building lines (along walls/structure, turning at 90°), not diagonally point-to-point. A straight-line (diagonal) measurement under-states the installed run; orthogonal Manhattan routing matches how the raceway is actually pulled and is the basis of every standard centre-line measurement.
Should vertical legs, risers, ceiling/tray drops to device height, and slab stub-ups, be added to the 2D plan length?
A floor-plan trace captures only the horizontal leg. The raceway also climbs and drops: receptacle drops to ~18 in AFF, switch drops to ~48 in AFF, risers up walls/columns, and slab stub-ups. These vertical legs are invisible on plan and are the most-missed conduit quantity; standard methods measure the developed (full installed) length, which includes them.
What default mounting heights should be assumed for receptacle and switch drops when no section is given?
Vertical-leg length depends on device height. NEC does not mandate a general-use height, but ADA/ICC A117.1 bound accessible devices to 15, 48 in AFF, and trade practice centers receptacles at ~18 in and switches at ~48 in. These defaults let the estimator compute drop lengths consistently.
How should a circuit be measured, detailed box-to-box centerline, or homerun-to-load-area plus an average per-device branch allowance?
Two legitimate methods coexist. The DETAILED method traces every box-to-box segment (most accurate, slow). The HOMERUN/AVERAGE method measures the homerun from the panel center to the farthest device on the circuit, then adds an average footage per device for the daisy-chain, far faster for repetitive branch wiring at the cost of precision. The choice flips by purpose: detailed for procurement, homerun-average acceptable for early bid.
When using the homerun-plus-average method, what average footage per device should be assumed?
Repetitive branch wiring is often estimated as a flat footage allowance per outlet/switch/fixture rather than traced. The figure varies widely by occupancy (residential vs commercial vs industrial), ceiling height, and device density, and is not fixed by any standard, so it must be exposed as a tunable, low-confidence default.
Related guides
Measure this trade automatically
Exayard reads your plans and produces a priced takeoff with these rules built in. Set your region and it applies the right standard.
Try Exayard free