Masonry takeoff
A measurement reference for masonry takeoff covering how brick, block, and stone walls are quantified: the two regional measurement models, opening deduction thresholds, unit and mortar coverage rates, grout, reinforcement, and the published standards behind each.
Masonry takeoff is the process of measuring brick, concrete block (CMU), and stone walls from drawings to produce buildable quantities. It falls under construction specification division 4. The work divides into two measurement models that reach a quantity by different routes, and the first decision on any project is which model applies.
This guide explains how each quantity is measured: the boundary the wall is taken on, the size at which openings start to be deducted, the coverage rates that turn wall area into a unit count, and how mortar, grout, reinforcement, lintels, and piers are handled. It is a reference on method and units, not a cost guide. The figures come from published standards and trade association documents, and regional differences are noted throughout.
The two measurement models
Most of the world measures masonry with a formal standard method of measurement, the route used by quantity surveyors. In the UK, RICS NRM2 Work Section 14 states the governing principle plainly: all walling is measured on the centre line of the wall. Walls are billed in square metres with the overall thickness stated, and the thicknesses used are nominal, meaning the unit size plus its mortar joint. Measuring on the centre line is efficient because external corners balance themselves out: the small over-measure at one return is exactly cancelled by the under-measure at the other, so corners need no separate adjustment. Australia and New Zealand (ANZSMM Section 12) and the civil engineering method CESMM4 follow the same family. Germany under VOB/C DIN 18330 bills by actual member dimensions rather than nominal.
The United States and Canada have no legal standard method. Instead the contractor route, defined by Brick Industry Association Technical Note 10 and Concrete Masonry and Hardscapes Association TEK 04-02A, uses the wall area method. You measure the net face area of each wall, which is the gross elevation area less openings, and multiply it by a units per square foot rate to get the brick or block count. Thickness is carried by the unit you choose, not by the area.
The two models do not interchange. A centre line square metre figure with a stated thickness already contains both the wall body and the corner material, while a net face area figure is just a surface that then drives a count. Picking the wrong model either double counts or drops the corner and return material.
Opening deductions
Every method keeps small voids in the wall, because the material saved by cutting around a small hole is eaten up by the labour of cutting and trimming. What differs is the size at which deductions begin, and the threshold spans a wide range by region. This is the single biggest regional fork in masonry takeoff.
Under RICS NRM2 you deduct voids larger than 0.50 m2, and there is a separate, smaller rule for flues in piers, which are not deducted at or below 0.10 m2. ANZSMM deducts only voids larger than 1.00 m2, so a 1.0 m by 0.5 m opening is explicitly kept. German VOB/C DIN 18330 is the most generous: for area billed work it over-measures, meaning it keeps, openings up to 2.50 m2, and for volume billed work it keeps recesses up to 0.50 m3. That materially inflates the billed area on facades with many windows. US practice has no codified threshold; it ignores anything under roughly 2 square feet and deducts larger openings net.
The deduction also flips by purpose, even within one region. A bid measured to a contract standard deducts exactly per the threshold. A material order leans gross, keeping small openings and adding reveal and jamb units so the pallet never falls short. A payment quantity is strict net with no ordering buffer. Reporting a material order quantity as if it were a measured for payment quantity overstates the bill.
Extra-over, cutting, and damp-proof course
Deducting an opening removes wall area, but the work around the opening is real and is captured separately. The standard method provides an extra-over item over walls for openings, measured by the linear metre of opening perimeter, covering sills, jambs, soffits, closing the cavity, and additional ties. US practice rolls this into a labour add on the wall rate instead. Omitting it under-prices any window-heavy facade even when the area deduction is correct.
Cutting is handled differently by region. Under NRM2 all rough and fair cutting and bonding to other work is deemed included in the walling rate and is not measured separately. US practice instead adds a cutting labour allowance and a higher unit waste band for cut-up walls. Taking a separate cutting item under a standard method bill double-pays work the rate already covers.
Damp-proof course is a separate masonry item, not absorbed into wall area. NRM2 measures damp-proof course up to 300 mm wide by the linear metre, with the width stated, and damp-proof course wider than 300 mm by the square metre. Cavity trays and flashings follow the section's split between deemed-included and separately measured items.
Cavity walls add their own items. The two leaves are each measured as walling, but forming the cavity is taken by the square metre with the cavity width stated, and the cavity insulation is taken by the square metre by type and thickness, or by the linear metre for a strip product. Wall ties bridging the cavity are counted.
Units, mortar, and coverage rates
The wall area rates are pure geometry: 144 square inches divided by the face area of one unit including its joint. A nominal 8 by 8 by 16 inch concrete block works out to 1.125 block per square foot. CMHA TEK 04-02A Table 1 lists 113 blocks per 100 square feet net, or 119 with a 5 percent waste allowance already included. Half-high 4 by 4 by 16 block doubles to 2.25 per square foot. Modular brick at a 3/8 inch joint is 6.75 per square foot, or 675 per 100 square feet, per BIA Technical Note 10 Table 4. Engineer modular brick is 5.63 per square foot, and closure or utility brick is about 4.5 per square foot.
Bond pattern can add units. BIA Table 6 gives exact corrections where header courses turn bricks to fill more of the same face area: common bond with headers every fifth course adds one fifth of a brick, English bond adds one half, and Flemish bond adds one third. Running bond and stack bond add nothing. Apply the bond correction before waste so the waste percentage compounds the corrected quantity, not the raw one.
Mortar yield is a function of unit size and joint thickness. BIA gives roughly 8.1 cubic feet per 1000 modular brick (5.5 cubic feet per 100 square feet) at a 3/8 inch joint, rising to 10.3 cubic feet per 1000 at a 1/2 inch joint. CMHA gives per-batch yields, where an 8-bag masonry cement mix with 1 ton of sand lays about 240 conventional blocks. Multi-leaf walls add a collar joint of about 3.13 cubic feet per 100 square feet. Hollow units laid with face-shell bedding use 25 to 35 percent less mortar, because mortar sits only on the face shells, so reduce by the void percentage. ASTM C270 is the governing mortar specification.
Grout for reinforced block
Grout volume swings by roughly six times depending on how much of the wall is filled, so the fill scope is the first thing to set before any coverage rate. Get the scope wrong and it becomes the largest single error in masonry material volume.
Once the fill scope and wall width are fixed, CMHA TEK 04-02A Table 3 gives the rate directly. The table assumes two-core units and bakes in 3 percent waste. For 8 inch block: solid grouted is 36.1 cubic feet per 100 square feet, which is about 2.1 cubic yards; cells grouted at 16 inches on centre is 18.1; at 24 inches is 12.1; at 32 inches is 9.1; and at 48 inches is 6.1. The full table covers 6, 8, 10, 12, and 14 inch wall widths.
Reinforcement, lintels, and piers
Reinforcement is derived from spacing, never drawn bar by bar. Vertical bars equal the wall length divided by the spacing, plus one for the end bar; omitting that final bar under-counts every wall. Each bar runs the full storey height plus a lap splice. TMS 402 computes the splice length by formula with code minimums and caps that vary by edition. The vertical spacing typically matches the grout spacing. Horizontal joint reinforcement, the ladder or truss wire, is taken as linear feet at typically 16 inches on centre. Bond beams are a counted or linear-foot grouted course. Veneer ties are counted, at a TMS 402 maximum of one per 2.67 square feet, and cavity wall ties at a maximum grid of 36 inches horizontal by 24 inches vertical.
Each sub-item takes its own unit. Reinforcing bars are measured by weight, joint reinforcement wire by length, and ties and anchors each. Reporting bar by length, or wire by weight, breaks the bill's unit and mis-prices the item.
Special members over openings are enumerated, not absorbed into the plain wall. NRM2 measures arches by their mean girth in metres, bands by the metre with the bond stated, and isolated piers, casings, and columns by the metre. Lintels are a separate each or linear-foot item. An element counts as an isolated pier, measured linear, rather than wall, measured by area, when its plan length is no more than four times its thickness, except where the short length is caused by an opening. US practice often rolls pilasters into wall square footage with a labour add. Whichever route is used, do not also count lintel block in the plain wall unit count, or you double-pay the head of the opening.
Waste and reporting units
Apply waste to the material, never to the boundary, and only after the bond and collar corrections. BIA states at least 5 percent on net brick, one of the few masonry waste figures given as an explicit clause, and 15 to 25 percent on net mortar to cover mixing, board, and cleanup losses. CMHA already bakes 5 percent into its 119-unit block figure and 3 percent into its grout table. Cut-up walls in practice carry a higher unit allowance, often in the range of 10 to 15 percent.
The reporting unit follows the regional model, and it is the same model choice expressed in the output. Standard method bills are stated in square metres with the thickness given, reinforcement by mass. The US wall area method reports per-100-square-foot tables, unit counts, and mortar and grout in cubic feet or cubic yards. Reporting a US count as if it were a standard method square metre, or the reverse, is the same model mismatch as picking the wrong boundary.
Exayard reads the drawings and applies these rules automatically, tracing each wall, cutting out the openings that cross the chosen deduction threshold, and converting the net result into the unit count, mortar, grout, and reinforcement quantities for the region in use.
How it varies by region
Standards of measurement differ by market. These defaults switch when you set your region in Exayard.
| What varies | Region | Default | Basis |
|---|---|---|---|
| Masonry wall-area boundary (centreline vs face vs net wall surface) | United Kingdom | Centreline, m² with thickness stated (formal SMM) | RICS NRM2 WS14 |
| Masonry wall-area boundary (centreline vs face vs net wall surface) | Australia / NZ | Centreline, m² with thickness stated (formal SMM) | ANZSMM Section 12 |
| Masonry wall-area boundary (centreline vs face vs net wall surface) | Europe | Actual member dimensions (m² thin / m³ thick) | VOB/C DIN 18330 |
| Masonry wall-area boundary (centreline vs face vs net wall surface) | United States | Net face area × units-per-SF (US wall-area method) | BIA TN 10; CMHA TEK 04-02A |
| Masonry wall-area boundary (centreline vs face vs net wall surface) | Canada | Net face area × units-per-SF (US wall-area method) | BIA/CMHA practice (US-aligned materials) |
| Masonry wall-area boundary (centreline vs face vs net wall surface) | International | Centreline, m² with thickness stated (formal SMM) | ICMS / RICS lineage |
| Masonry opening / void deduction threshold (area) | United Kingdom | 0.5 m2 | RICS NRM2 WS14 |
| Masonry opening / void deduction threshold (area) | Australia / NZ | 1 m2 | ANZSMM Section 12 |
| Masonry opening / void deduction threshold (area) | Europe | 2.5 m2 | VOB/C DIN 18330 |
| Masonry opening / void deduction threshold (area) | United States | 0.186 m2 | US estimating practice (convention) |
| Masonry opening / void deduction threshold (area) | Canada | 0.186 m2 | US-aligned practice |
| Masonry opening / void deduction threshold (area) | International | 0.5 m2 | ICMS / NRM2 lineage |
| Lintel / arch / band measurement (separate item vs absorbed) | United Kingdom | Separate LF/each item | RICS NRM2 WS14 |
| Lintel / arch / band measurement (separate item vs absorbed) | Australia / NZ | Separate LF/each item | ANZSMM Section 12 |
| Lintel / arch / band measurement (separate item vs absorbed) | United States | Separate LF/each item | CMHA TEK 17-02A (precast lintels) |
| Unit of measure and rounding for masonry quantities | United Kingdom | m² with thickness stated (SMM) | RICS NRM2 WS14 |
| Unit of measure and rounding for masonry quantities | Australia / NZ | m² with thickness stated (SMM) | ANZSMM Section 12 |
| Unit of measure and rounding for masonry quantities | Europe | m² with thickness stated (SMM) | VOB/C DIN 18330 |
| Unit of measure and rounding for masonry quantities | United States | SF / unit counts / ft³-CY (US) | CMHA TEK 04-02A; BIA TN 10 |
| Unit of measure and rounding for masonry quantities | Canada | SF / unit counts / ft³-CY (US) | US-aligned materials |
| Unit of measure and rounding for masonry quantities | International | m² with thickness stated (SMM) | ICMS |
Key terms
- Masonry wall-area boundary (centreline vs face vs net wall surface)
- The two regional models reach a buildable quantity by different routes and do not interchange.
- Masonry opening / void deduction threshold (area)
- Everyone keeps SMALL voids (the unit/cutting saving is eaten by the labour of cutting around the hole), but the threshold spans an order of magnitude by region, which is the single biggest regional fork in masonry takeo…
- Opening deduction by purpose (net bid vs material order vs payment)
- The deduction flips by PURPOSE even within one region.
- Wall thickness basis (nominal vs specified/actual)
- SMM thicknesses are NOMINAL (unit size plus its mortar joint), e.g.
- Units per square foot of wall (CMU and brick coursing)
- The wall-area rates are pure geometry (144 in² ÷ face-area-with-joint).
- Bond-pattern unit correction (headers add units)
- Header courses turn bricks 90° so more units fill the same face area.
- Unit (brick/block) waste and breakage allowance
- Apply waste to material, never to the boundary, and only after bond/collar corrections.
- Mortar quantity per unit area / per 1000 units
- Mortar yield is a function of unit size and joint thickness.
- Mortar waste allowance
- Mortar waste is much higher than unit waste because of mixing/board/cleanup losses.
- Grout fill scope (solid vs partial by reinforcement spacing)
- Grout swings ~6× by fill scope, so this is the first thing to set before any coverage rate.
- Grout coverage rate (ft3 per 100 SF by wall width and spacing)
- Once fill scope and wall width are fixed, CMHA TEK 04-02A Table 3 gives the rate directly (two-core units, 3% waste).
- Vertical reinforcement spacing basis (bars-from-spacing)
- Reinforcement is derived from spacing, never drawn bar-by-bar: vertical bars = wall length ÷ spacing + 1, each full storey height plus a lap splice.
Standards referenced
- RICS NRM2, Work Section 14 Masonry
- Brick Industry Association Technical Note 10
- CMHA/NCMA TEK 04-02A, Estimating Concrete Masonry Materials
- ANZSMM 2018
- VOB/C DIN 18330
- ASTM C270
- CMHA/NCMA TEK 03-02A, Grouting Concrete Masonry Walls
- CMHA/NCMA TEK 12-02B, 16 in o.c. typical
- TMS 402/602
- Brick Industry Association Technical Note 44B, Wall Ties for Brick Masonry
- ASTM A615/A615M, nominal mass per unit length
- CMHA/NCMA TEK 17-02A, Precast Concrete Lintels
Frequently asked questions
How is masonry wall quantity measured: on the wall centreline (formal SMM), or as the net face area (US wall-area method)?
The two regional models reach a buildable quantity by different routes and do not interchange. Formal SMM (RICS NRM2 WS14: 'All walling is measured on the centre line') bills m² with the overall thickness stated; the centreline self-balances external angles (over-measure at one return cancels the under-measure at the other), so corners need no separate adjustment and the figure already contains its corner material. The US wall-area method (BIA TN 10 / CMHA TEK 04-02A) measur…
At what opening/void size do you start deducting from masonry wall area, and is the rule m²-area or volume-based?
Everyone keeps SMALL voids (the unit/cutting saving is eaten by the labour of cutting around the hole), but the threshold spans an order of magnitude by region, which is the single biggest regional fork in masonry takeoff. NRM2 deducts voids over 0.50 m² (flues in piers have their own ≤ 0.10 m² rule); ANZSMM deducts over 1.00 m²; German VOB/C DIN 18330 over-measures (keeps) openings up to 2.50 m² for m²-billed work, materially inflating billed area on window-heavy facades; t…
Should opening deductions follow the contract SMM, or be relaxed for material ordering / progress billing?
The deduction flips by PURPOSE even within one region. A bid measured to a contract SMM deducts exactly per the threshold. A material order leans gross (keep small openings, add reveal/jamb units so the pallet never falls short). A payment quantity is strict SMM net with no ordering buffer. Reporting a material-order quantity as if it were a measured-for-payment net quantity overstates the bill.
When stating masonry wall thickness, use the nominal dimension or the specified/actual dimension?
SMM thicknesses are NOMINAL (unit size plus its mortar joint), e.g. an 8-in CMU is nominally 8 in but actually 7-5/8 in. The wall-area method also carries thickness by the nominal unit chosen. Mixing nominal and actual mislabels the wall band and can mis-route the per-SF coverage rate (which is itself derived from nominal face-with-joint geometry). German VOB/C is the exception that bills by ACTUAL member dimensions.
What unit-coverage rate converts net wall area to a unit count (brick/SF, block/SF)?
The wall-area rates are pure geometry (144 in² ÷ face-area-with-joint). CMU 8×8×16 nominal = 1.125 block/SF (CMHA TEK 04-02A: 113 per 100 SF net, 119 with 5% waste). Half-high 4×4×16 = 2.25/SF. Modular brick (4×2⅔×8) at a 3/8" joint = 6.75/SF (BIA TN 10 Table 4); the commonly-quoted 6.86/SF is the same number at a slightly thinner effective joint. Engineer modular 5.63/SF, closure/utility ~4.5/SF. The rate is a deterministic function of the chosen unit size and joint, so it…
Does the bond pattern (running, Flemish, English, common-with-headers) add units beyond the running-bond rate?
Header courses turn bricks 90° so more units fill the same face area. BIA TN 10 Table 6 gives exact corrections: common bond with headers every 5th course +1/5 brick, English bond +1/2, Flemish +1/3. Running bond and stack bond add nothing. Apply the correction BEFORE waste so the waste percentage compounds the corrected (not the raw) quantity.
Related guides
Measure this trade automatically
Exayard reads your plans and produces a priced takeoff with these rules built in. Set your region and it applies the right standard.
Try Exayard free